Sprite icons

NOT FOR SALE YET-Temperature-based control | AC fan | electric heater

No one has commented on this product yet, please be the first (look below), we appreciate your opinion!
Article code AH-D-000009
Current stock 2 U.
Factory lead time 5 Week(s)

Solution description

State-of-the-art temperature-based supply-only air handling unit control. Fan with an AC 3-phase 400 V motor and maximum current 9,5 A. The AHU features a three-step electric heater with 3-phase 400 V supply and total power 15 kW. It has two levels of overheating protection. Differential pressure sensors are used to monitor fan operation and filter condition. Air damper actuator control.

Additional specifications and description

This solution is designed to monitor and control air handling unit that is shown on schematic below:
Supply AHU schematics with numeration of specific parts

Air handling unit consists of four parts, which are: supply air damper (1), supply air filter (2), supply fan (3) and electric air heater (4).

Control logic description
Operation of air handling unit is automatic and based on sensor readings. There are predefined logics for the different parts of the AHU.

Supply air damper
opens 30 seconds before supply fan starts. This is crucial for high airflow AHUs as it prevents possible damage to the air damper.

Air filter
condition is measured via differential pressure transmitter HPS-M-1K0-2. The measurements are transferred to HVAC controller DRPUM (master device). In case the pressure drop on the filter exceeds the setpoint, user will be notified to perform their maintenance. However, the AHU continues its operation regardless of the filter condition.

Supply fan
speed can be controlled manually or automatically via frequency inverter FI-E-44095E2. We also use differential pressure transmitter HPS-M-1K0-2 to control fan operation. In case of mechanical fan failure (jamming, bearing breakdown), there will be no pressure drop and the master device will produce the following steps: switch off frequency inverter, close air damper and inform the user about the error. In automatic mode HPS-M-1K0-2 can be used to maintain certain pressure difference.

Electric air heater
operation is controlled using duct temperature and humidity sensor DSTHM-2 in combination with Modbus RTU IO module DIO-M-D4. If the measured temperature is higher, than the desired one, electric heater is switched off. Otherwise, if the measured temperature falls below the desired value, the first step of electric heater is activated. If the resulting temperature is still lower than desired one, the next step will start operating. When the resulting temperature becomes exceeds the desired value, the steps are switched off one by one. Electric air heater won't switch on if there is no certain pressure drop on the fan.
Electric air heater has two levels of overheating protection. One of them is triggered when the casing temperature reaches 60°C and it restarts automatically. The second level activates when the enclosure heats up to 90°C and can only be restarted manually.
To prevent overheating when the AHU switches off, it is conducted in the following steps:
  • The electric heater is switched off;
  • The damper remains open, and the fan continues to operate for three minutes to cool down the air heater;
  • The fan is switched off, and the air damper is closed.
System configuration
This solution includes network gateway DIG-M-2 that provides the user with the access to the online HVAC platform – SenteraWeb. The connection can be established via an Ethernet cable or a Wi-Fi network. It allows to remotely monitor data and adjust settings of the connected HVAC devices via internet. Data logging is also possible.

Components of this solution

Article code
Quantity
Description

DRPUM

1 U.

The DRPUM is a universal HVAC controller engineered for efficiency and flexibility, which seamlessly integrates into your HVAC setup. It features RJ45 and RJ12 sockets for connecting Modbus RTU slave devices. A single network cable distributes both supply voltage and Modbus RTU communication across your entire network of devices. There are two Modbus channels - one dedicated to linking with a Building Management System or SenteraWeb Cloud services, and another to connect up to 247 slave devices. The DRPUM is delivered without pre-installed firmware, but you can download the appropriate firmware according to your application. The device is compact and efficient, its enclosure is DIN rail mounted providing easy mounting and neat organization of your HVAC control system.

DRPS8-24-40

1 U.

A 24-volt switched-mode power supply (SMPS) is a type of electronic power supply that converts electrical energy from one voltage level to another. This supply module with the convenience of DIN rail mounting is a versatile solution for various applications across different industries. Whether you're managing automation systems (e.g. heating or ventilation systems), control panels, or electronic devices, this power supply is the key to your reliable and secure operation. This module accepts an input voltage of 85–264 VAC / 50–60 Hz. The maximum load on this switched mode power supply is 40 Watts. The loads can be connected via the terminal block or via the RJ45 connector. Because it is designed to be mounted on a DIN rail, integrating the power supply into your electrical cabinet will be simpler. The device is shielded from dust and dirt by the IP20 protection provided by the enclosure. In addition, the safety of your electrical installation is increased by the overload and overvoltage protection. Comparing to linear power supplies, switching power supplies are more efficient, lighter, and more compact (due to their transformer-free design). Because of their high efficiency, they produce less heat and contribute to greater energy savings.

DMDBM22

1 U.

This is a distribution box for Modbus RTU communication and supply voltage. It can be used to interconnect Sentera devices. It has 10 channels for 24 VDC powered devices and 12 channels for 3,3 VDC powered devices. Modbus RTU communication and 24 VDC supply voltage are transmitted via the RJ45 sockets. Modbus RTU communication and 3,3 VDC supply voltage are transmitted via the RJ12 sockets. External power supply is required for both 24 VDC and 3,3 VDC supply.

ODTHM

1 U.

Outdoor temperature and humidity sensor for HVAC applications. The power supply voltage is 24 V DC PoM, which means that Modbus RTU communication and a 24 V DC power supply can be connected using a single RJ45 connector. The sensor measures temperature, relative humidity, and the amount of light in the environment. It is suitable for use in harsh environments or in outdoor applications. Modbus RTU communication is used to transmit the measured values and it allows you to change all of the settings. The ambient light sensor can be used in many applications to control the ventilation system based on the occupancy of the room.

HPS-M-1K0 -2

1 U.

This HVAC sensor measures differential pressure within the range from 0 to 1.000 Pa and operates with a supply voltage of 24 VDC, Power over Modbus or PoM – both Modbus RTU communication and power supply are connected via the RJ45 socket using a single cable. This sensor can also measure air volume flow or air velocity. The measured value is available via Modbus RTU communication. The four LED indicators provide a visual indication of the sensor status and the measured values. The differential pressure range and all other settings are adjusted via Modbus RTU.

HPS-M-1K0 -2

1 U.

This HVAC sensor measures differential pressure within the range from 0 to 1.000 Pa and operates with a supply voltage of 24 VDC, Power over Modbus or PoM – both Modbus RTU communication and power supply are connected via the RJ45 socket using a single cable. This sensor can also measure air volume flow or air velocity. The measured value is available via Modbus RTU communication. The four LED indicators provide a visual indication of the sensor status and the measured values. The differential pressure range and all other settings are adjusted via Modbus RTU.

DSTHM-2

1 U.

This HVAC transmitter measures temperature and relative humidity in air ducts. The dew point is calculated using the measured values. The power supply is 24 V DC PoM. This means that one RJ45 connector can connect Modbus RTU communication and a 24 V DC power supply. The sensor makes use of Modbus RTU communication to transmit the measured values. It can also be used to change several other the settings.

DIG-M-2

1 U.

The DIG-M-2 Gateway is designed to connect Sentera devices to the SenteraWeb online HVAC platform. It provides a means of communication between the devices and the platform, allowing remote monitoring, data logging and adjustment of settings via the internet. The gateway can be connected to the Sentera devices using either an Ethernet cable or a Wi-Fi network. It is equipped with an RJ45 connector, which serves as a connection point for both Modbus RTU communication and the 24 VDC supply voltage. This enables the devices to communicate with the gateway and receive power from it. Once connected to the SenteraWeb platform, the gateway enables remote access and control of the connected HVAC devices. Users can monitor data, such as temperature, humidity and other relevant parameters, and make adjustments to the settings as needed. The platform also supports data logging, allowing for historical data analysis and system optimization. The gateway is designed to be mounted on a DIN rail. This allows for easy installation and integration into existing setups.

FI-E44095E2

1 U.

Variable speed drive to control 3ph 400 Volt motors. This VSD is particularly simple to use. For most applications it is not necessary to change the default settings. That is why this variable speed drive is ideal for controlling fans and pumps in HVAC applications. The required supply voltage is three-phase 400 Volt. Various types of three-phase 400 Volt motors can be controlled: IE3 or IE4 induction motors, permanent magnet motors, brushless DC or synchronous reluctance motors. One or multiple motors with a (combined) maximum current of 9.5 A can be controlled by this drive. Motor speed can be set via the intuitive keypad or via the inputs. Configuration is simplified via 14 basic parameters and application macro functions. The enclosure can be DIN rail mounted in an electrical cabinet. It offers an IP20 protection against ingress of dust. The integrated EMC filter is Class C1. Manufacturers code: ODE-3-240095-3F42

DIO-M-D4

1 U.

This is an Input-Output module for Modbus RTU networks. It has 4 digital inputs and 4 digital outputs. The digital outputs are activated via a Modbus RTU. The status of the digital inputs is translated into Modbus RTU registers. The supply voltage is 24 VDC, Power over Modbus. This means that both Modbus RTU communication and the supply voltage can be connected via the RJ45 socket. The enclosure is DIN rail mounted. It offers an IP30 protection degree against ingress of dust and moisture.

ADPT-3SM-FI

1 U.

Adapter to connect Invertek frequency inverter (FI-E and FISE series) to a Sentera Modbus RTU network. The Invertek RS485 communication is converted into Modbus RTU communication. This makes it possible for the Sentera HVAC controllers to control the Invertek frequency inverters via Modbus RTU. One integrated control solution for your HVAC or ventilation system.

MDB-M-6

1 U.

This Modbus RTU distribution box has six RJ45 sockets. These six RJ45 sockets are internally connected (parallel connection). It distributes Modbus RTU communication and 24 VDC power supply between the connected devices and is used to interconnect Sentera devices. Via the Sentera PoM connection, both Modbus RTU communication and 24 VDC power supply are distributed via a single UTP cable with an RJ45 connector. The plastic enclosure offers an IP65 protection against the ingress dust and water. It can be wall-mounted.

PSET-PVC-200

2 U.

Set of nozzles and PVC tubes to connect a differential pressure sensor or controller to the ductwork. It contains 2 plastic nozzles (L 66.6 mm, D 6 mm) and 2 flexible, transparent PVC tubes with a length of 2 m and a maximum working pressure of 10.000 Pa. The screws to fix the nozzles in standard ductworks are also included. This set is designed for HVAC applications and can be used in combination with differential pressure transmitters, controllers or switches.

DRM-M-02

1 U.

The DRM-M-02 are relay output modules for Modbus networks. They are equipped with 2 C/O relays with a normally open and normally closed contact. The relay status can be controlled via the Modbus RTU registers. Each relay has a switching capacity of 5 A (resistive) at a voltage of 220 VDC / 250 VAC. The device is designed for mounting on a DIN rail and is powered with 24 VDC, Power over Modbus via an RJ45 connection for both Modbus RTU data exchange and supply voltage running over one UTP cable.

More Less

Remarks, reviews & ratings

There are no reviews added yet. Please don't hesitate and be the first! We value your opinion.
Add a remark or a review and rating.
0
Report an error